Energy-led retrofitting of solid wall dwellings - technical and user perspectives on airtightness
conference contribution
posted on 2012-03-30, 09:08 authored by Phil Banfill, Sophie Simpson, Victoria HainesVictoria Haines, Becky MallabandMechanical ventilation with heat recovery (MVHR) is increasingly being promoted in
the UK as a means of reducing the CO2 emissions from dwellings, and installers report
growing activity in the retrofit market. In parallel with a survey of householder
preferences and practices, the behaviour of a whole-house MVHR system installed in
an experimental house, purpose built to typical 1930s standards, has been simulated.
The range of air permeability values corresponded to those achieved in a retrofit
upgrading process carried out on the house. In the house considered, air permeability,
as measured in a 50 Pa pressurisation test, must be reduced below 5 m3/m2.h for
MVHR to make an overall energy and CO2 saving. This required a level of disruption
that would be unlikely to be tolerated by owners of solid wall dwellings.
History
School
- Design
Citation
BANFILL, P. ... et al., 2011. Energy-led retrofitting of solid wall dwellings - technical and user perspectives on airtightness. IN: Ruddock, L. ... et al. (eds.) COBRA 2011 - Proceedings of the RICS Construction and Property Conference, 12th - 13th September 2011, University of Salford, Manchester, UK, pp.430-440.Publisher
COBRA 2011 - the Royal Institution of Chartered Surveyors International Research ConferenceVersion
- AM (Accepted Manuscript)
Publication date
2011Notes
This conference paper was presented at COBRA 2011, the Royal Institution of Chartered Surveyors' (RICS) international research conference: http://site.cibworld.nl/dl/publications/COBRA_2011.pdfISBN
9781907842191Publisher version
Language
- en