This study involves a detailed analysis of a mechanically ventilated heat recovery (MVHR) system installed as a case study retrofit project in a UK test dwelling. Comparisons of predicted and in situ performance are made through the calculation of a theoretical and practical heat loss coefficient value (HLC). Analysis revealed underperformance in the installed MVHR system, as compared to predicted data. Issues were identified in the installation and function of the control unit and ductwork. Improvement work enabled the system to function more closely to optimum performance levels. However, discrepancies still existed between the predicted and actual HLC values, which were largely accounted for through theoretical heat loss calculations attributable to slight imbalances within the system supply and extract rates. When normalised, the data still showed an unaccounted heat loss of approximately 6 W/K in both MVHR tests. The study reinforces the need for high quality MVHR installation and commissioning work, which is critical to ensure that a system can perform to the optimum levels specified in manufacturer literature. Education and training throughout the supply chain is essential in achieving this, as system inefficiencies can lead to unnecessary heat losses resulting from increased levels of air infiltration or leakage.
Funding
This work forms part ofthe E.On funded Retrofit Research House
Project and the CALEBRE Project which is funded by the Research
Councils UK and E.ON.
History
School
Architecture, Building and Civil Engineering
Published in
Energy and Buildings
Volume
110
Pages
220 - 228
Citation
WHITE, J. ... et al., 2016. Performance evaluation of a mechanically ventilated heat recovery (MVHR) system as part of a series of UK residential energy retrofit measures. Energy and Buildings, 110, pp. 220 - 228.
This work is made available according to the conditions of the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International (CC BY-NC-ND 4.0) licence. Full details of this licence are available at: https://creativecommons.org/licenses/by-nc-nd/4.0/