posted on 2010-10-28, 13:50authored byPeter A. Jones
A current limitation on the structural use of steel fibre reinforced sprayed concrete (that
equally applies to cast steel fibre reinforced concrete) is a distinct lack of accepted design
rationales and codes of practice. The research presented here describes the development of
a model, based on conventional principles of mechanics, for predicting the flexure behaviour
of a wet process sprayed concrete reinforced with deformed steel fibres. The model uses a
stress-block diagram to represent the stresses (and resultant forces) that develop at a
cracked section by three discrete stress zones: (a) a compressive zone; (b) an uncracked
tensile zone; and (3) a cracked tensile zone. By using this concept it is shown that the
stress-block diagram, and hence flexural behaviour, is a function of six principal parameters:
the compressive stress-strain relation; the tensile stress-strain relation; fibre pull-out
behaviour; the number and distribution of fibres across the crack in terms of their positions,
orientations and embedment lengths; and the strain/crack-width profile in relation to the
deflection of the beam.
An experimental investigation was undertaken to obtain relationships for these parameters.
Five tests were identified and developed as part of this investigation: a single fibre pull-out
test; a compression test; a strain analysis test; a fibre distribution analysis test; and a flexural
toughness test. The majority of the investigation used cast (as opposed to sprayed)
specimens so that the test variables under investigation could be better controlled. Spraying
trials were also successfully undertaken to demonstrate the pumpability and sprayability of
the adopted mixes and to verify the use of the model for both cast and sprayed specimens.
The results of the modelling analysis showed a reasonable agreement between the model
predictions and experimental results in terms of the load-deflection response. However, the
accuracy of the model is probably unacceptable for it to be currently used in design. A
subsequent analysis highlighted the single fibre pull-out test and the sensitivity of the strain
analysis tests as being the mai n cause of the discrepancies. As a result, recommendations
are made for how the model might be improved.
Overall this research has provided a valuable insight into the reinforcing mechanisms,
fracture processes and characteristics of failure associated with the flexural behaviour of
steel fibre reinforced concrete. It is envisaged that the proposed model could form the basis
of a design rationale which requires only the matrix strength, fibre type, fibre content, beam
size and loading geometry as design input parameters. Consequently, it could offer a much
needed link between flexural toughness performance and structural design, by allowing
designers to make informed choices regarding the mix design in order to meet the ultimate
and serviceability requirements of a particular application.